3 Description of the eSite x10
3.1 eSite x10 introduction
The eSite x10 is a hybrid power unit that supplies a load with stable power by combining software-defined hybrid battery control with solar power, intelligent grid power harvesting and/or optimal genset control. The preconfiguration lets up to three tenants with separate load measurements connect to the eSite x10. The site configuration depends on the site prerequisites.
The eSite x10 can be supplied with AC power from genset and grid and with DC supply from solar panels. The supplied power is used to carry the customer load and to charge a battery bank. The AC supply is converted through rectifiers in the Main Compartment into -48V DC. The switching between the connected power sources is automatic. The DC supply is converted through solar converters in the Main Compartment into -48V DC. The eSite x10 starts and stops the genset automatically based on the state of the battery bank and the associated charge strategy. If solar arrays are part of the configuration, they are always in operation and supplies power when the weather conditions are right.
The Main Compartment contains all central parts and functions of the eSite x10. The Main Compartment is sealed and tamper-proof, and preconfigured when supplied. The Main Compartment does not contain serviceable parts.
The Connection Compartment is the only connection point access to the eSite x10. The Connection Compartment is designed to make power connectivity simple and intuitive, facilitating a smooth and easy installation/site commissioning of the system.
⚠️ Warning
Do not open or make modifications to the Main Compartment. This is strictly prohibited and can be a threat to life.
🚨 Caution
If there is a failure or performance deviation, the Main Compartment must be sent to the nearest eSite Power Systems approved service centre.
🚨 Caution
The Main Compartment must be connected to the Connection Compartment only unless a written statement from eSite Power Systems permits other connectivity devices. No third party connection device may be used without explicit consent and approval by eSite Power Systems. The Connection Compartment and the power connectivity is subject to regulatory control by eSite Power Systems.
Figure 3.1 shows an overview of a mounted eSite x10 unit with the most important features identified as follows.
A Mounting Frame
B Main Compartment including Lower Main
C Product marking plate
D Visual indication – green LED
E Visual indication – red LED
F Connection Compartment
G Connection Compartment lid

Figure 3.2 shows an overview of a complete site setup with the eSite x10 and associated systems on site, identified as follows.
A eSite x10
B eSite Tools
C Genset
D Solar panels
E Grid
F Battery cabinet and battery bank
G Customer load

3.2 Technical specifications
| AC Input | |
|---|---|
| Nominal AC input | 230–250 V AC |
| Permitted AC input range | 85–300 V AC |
| Frequency | 45–65 Hz |
| Input current | 3 x 19 A |
| Power factor | >0.99 |
| THD | <5 % at 230 V AC, 100 % load |
| Input voltage derating | Linear derating for each phase, 3500 W @ 190 V AC, 1500W @ 85V |
| Protection | Varistor transient protection of all phases towards neutral. Varistor and GDT transient protection towards protective earth. Solid state transfer switch for long duration over voltages. |
| DC Output | |
|---|---|
| Operational range | -42 – -58 V DC |
| Rectifier capacity | 3 x 3500 W |
| Output power | 10500 W |
| Current | 195 A @ 54 V |
| Max current | 235 A |
Output Power Derating by Ambient Temperature, | Continuous power at 45 ⁰C: 9750 W |
Output Power Derating by Ambient Temperature, Cyclic Operation (230 VAC). | Full power at 45 ⁰C for 65 min, then derating to 9750 W |
| Rectifier peak efficiency | 95 %* |
| DC power system efficiency | 94 % |
| DC power port for Low Priority Load | 7000 W |
| DC power port for High Priority Load | 3000 W |
*The value includes an integrated static transfer switch.
| Solar Converter | |
|---|---|
| Nominal input voltage | 125 V DC |
| Permitted input voltage range | 50–150 V DC |
| Maximum input current | 3 x 20 A |
| Power conversion capacity | 6,6 kW |
| Power conversion peak efficiency | > 96.5 % |
| Environmental | |
|---|---|
| Nominal Temperature | - 20 – + 45 °C |
| Operating Temperature | - 20 – + 50 °C |
| Storage Temperature | - 40 – + 70 °C |
| Relative Humidity | 0–99 % |
| Cooling | Passive Convection Cooling |
| IP Code | Main Compartment IP65 |
| EMC | ETSI EN 300 386 V1.6.1 |
| Safety | IEC/EN 60950-1:2005+A1+A11+A12+A |
| Environmental standards | ETSI 300 019-1-2 Class 2.3 Public Transportation |
| MTBF | >350 000 h (@T ambient 25 °C) according to Siemens SN29500 |
| Communication ports | |
|---|---|
| I/O | 4 Digital outputs; 8 Digital inputs; 4 Analog inputs |
| External Bus | CAN; RS485; Ethernet |
| WLAN | Wi-Fi access point as service interface; SMA Connector |
| Radio modem | UMTS/HSPA: 850/900/1900/2100 MHz |
| Service port | Ethernet |
| Isolation | 3.0 kV AC mains – Earth |
Figures 3.3 and 3.4 shows the rectifier characteristics for derating due to high temperature and power efficiency.