Micro Documentation

4 eSite Web

4.1 Overview

eSite Web is accessed on site via a laptop or a smartphone using Wi-Fi or LAN cable. It provides the user with an overview of the status of eSite x10 and active alarms. It also offers a possibility to configure eSite x10 (see figure 4.1).

Figure 4.1. eSite Web Configuration pages.

eSite Web allows two user levels. Each user requires a user name and a password.

The default passwords is provided by eSite Power Systems.

The passwords can be changed by the Admin user.

User levelAccess
OperatorView data and alarms (read only).
AdminView data and alarms. Configure the system. Update the system and download data.

For configurations, see section Configurations.

For alarm functionality, see section Alarms.

From the first page pages with more detailed information is reached. Click the icons on the menu bar to reach the detailed information and to configure the system.

The eSite Web header (see figure 4.2) contains the following basic information about the specific eSite x10 system.

Figure 4.2. eSite Web header.
Information shownPossible values/inputComment
Site nameText input from configuration.Usually town or area where eSite x10 is located.
Site IDText input from configuration.Connects eSite x10 to eSite Tools.
System modeAuto / Auto Full Charge / Safe Mode / ManualDescribes in what mode eSite x10 is currently operating.
Local date and timeYear - Month - Day Hour : min : secPresent local date and time.
eSite Tools server connectionNot configured / No connection to server / SynchronizedIndicates the status of the connection to eSite Tools server.
Battery statusVolt and state of charge.For more information see section "Battery information".
Estimated time to next genset startHours / MinutesShows the time left until genset starts and at what state of charge this occurs. This information is only visible when charge strategies Static SOC or Partial SOC are active.

4.2 Battery information

The Battery menu provides the information in the table below. For further information about the batteries, read the reference Batteries.

Information shownPossible valuesComment
Battery typeType name selected from configuration.The battery type is shown in the table header.
State of Charge (SOC)%Shows battery state of charge. 0 % = empty batteries with no energy left. 100 % = fully charged.
Battery stateDischarge / Charge / Absorb / Equalized / Fully charged / Fall backFor more information see Battery states
Battery temperature°CReads battery temperature from sensor placed in the battery bank.
Total throughputkWhTotal energy that has passed through the battery bank(s), based on the discharge current. Since commissioning or last reset. Can be reset under battery configuration.
Battery charge currentATotal current going in and out of the battery bank(s). A negative current indicates discharge and a positive current indicates charge.
Battery capacityAhTotal battery bank max capacity. Depending on battery configuration this either shows the specified maximum capacity or dynamically estimates the maximum capacity.
Charge modeNormal charge / Full charge / Extended Full Charge / Safe Mode / Ramp Up / SynchronizeShows what charge mode that is currently active.
Charge requestNot active / ActiveWhen active, eSite requires power to charge the batteries.
Cooling Fan statusOff / On / Forced On / Fall backThe Fan can be forced on via command see Configuration pages. Fall back status means that Ambient- and/or Battery-sensor are disconnected.
Battery charge strategyVoltage control / Static SOC/ Partial SOC/ Li-ion Static / UPS AC ModeShows what charge strategy is currently active. The battery charge strategy can be configured, for more information see section Batteries.
Voltage Cycle StartVVoltage level to trigger charge cycle.
Voltage Cycle StopVVoltage level for charge done.
Voltage Cycle Stop CurrentACharge current for charge done.
Voltage Cycle Stop TimesecCharge time after reaching stop voltage and stop current.
Voltage Cycle Full Charge Time / Time LeftsecTime between full charge cycles and time left until a full charge is triggered.
Voltage Cycle Full Charge Energy / Energy LeftkWhEnergy throughput between full charge cycles and throughput left until a full charge is triggered.
Static SOC Window start%SOC level to start charge.
Static SOC Window stop%SOC level to stop charge.
Static SOC Window Full Charge Time / Time LeftsecTime between full charge cycles and time left until a full charge is triggered.
Static SOC Window Full Charge Energy / Energy LeftkWhEnergy throughput between full charge cycles and throughput left until a full charge is triggered.
Partial SOC Window%Falling SOC window to start charging.
Partial SOC Stop CurrentACurrent level for charge done.
Partial SOC Stop VoltageVVoltage level to stop charging.
Partial SOC Stop SOC%Falling SOC window between charge cycles.
Partial SOC Full Charge VoltageVLower voltage level to force full charge.
Partial SOC Full Charge Time / Time LeftsecTime between full charge cycles and time left until a full charge is triggered.
Partial SOC Full Charge Energy / Energy LeftkWhEnergy throughput between full charge cycles and throughput left until a full charge is triggered.
Hybrid Shifting Statusenum0=Not active, 1=Active. For more information see section Hybrid Shifting.
Peak Load Shifting statusenum0=Not active, 1=Active. For more information see section Peak Load Shifting.
BMU data / StatusenumThe status can be: "Invalid", "Not installed", "No communication", "Operational", "Not Operational".
BMU data / SOC%State of Charge for each BMU.
BMU data / SoH%State of Health for each BMU.
BMU data / CurrentATotal current going in and out of the battery BMU. A negative current indicates discharge and a positive current indicates charge.
BMU data / Max Cell VoltageVMaximum Cell Voltage.
BMU data / Min Cell VoltageVMinimum Cell Voltage.
BMU data / Total VoltageVTotal Voltage of the Module.
BMU data / Charge mode-Charge mode of the module can be charge or discharge.

4.3 Genset information

Two gensets can simultaneously be connected to eSite x10. The configured gensets are visible under the Genset menu. The Genset menu provides the information shown in the table below. For further information about Gensets read the reference in section Genset.

Information shownPossible valuesComment
Operational modeForced on / All AC sources forced off / AutoActual genset operational mode commanded by the eSite x10.
Night Silence modeDisabled / Inactive / Pre charge / Silent period active / Silent period abortedIf Night Silence mode is active, the genset is inhibited until it leaves night silence or Night Silence is aborted.
Genset modeReady / Start Request / Warm-up / Ramp Up / Running / Ramp Down / Cool Down / OffeSite controlled state of the genset(s). A counter shows for how long a mode has been active, for example for Running, or how many seconds that are left, for example for Warmup.
Actual stateStopped / RunningDetected state of the genset.
Unexpected genset startYes / NoGenset is running without eSite requesting it to run.
Power requestWRequested power from the genset, kept at maximum capacity rating.
Genset powerWProduced power from genset.
Produced energykWhProduced energy since commissioning or last reset.
Produced currentAProduced current from genset.
L1V (Hz)Voltage and frequency.
L2V (Hz)Voltage and frequency.
L3V (Hz)Voltage and frequency.
Genset service countdownhTime left until genset service.
Total genset run hourshRuntime since eSite x installation.
Tank X volumelPresent volume in tank.
Tank X max volumelThe maximum volume of the tank is configured under the configuration menu Fuel monitoring.

4.4 Solar information

Three solar arrays at a time can be connected to eSite x10. All connected solar arrays are visible under the Solar menu. The Solar menu provides the information shown in the table below. For further information about solar arrays read the reference in section Solar management.

Information shownPossible valuesComment
Total powerWTotal produced power from the solar converters.
Total energykWhTotal produced energy from the solar converters since installation/last energy reset.
Total currentATotal produced output current from the solar converters.
Array voltage (Solar x)VVoltage of a specific array.
Output power (Solar x)WProduced power from the array.

4.5 Grid information

The Grid menu provides the information shown in the table below. For further information about Grid read the reference in section Grid.

Information shownPossible valuesComment
Grid statusInvalid / Inhibited / Partial / OkInvalid when no grid power is available, Inhibited if Green Power mode is configured to inhibit grid power, Partial 1 or 2 phases are not available.
User grid power0–10500 WPower drawn from grid.
Total used grid energykWhEnergy drawn from grid since installation of the site.
Grid currentAProduced current from grid.
L1V (Hz)Voltage and frequency.
L2V (Hz)Voltage and frequency.
L3V (Hz)Voltage and frequency.
Grid fuseAConfigured size of the maximum rating of the fuse on site.

4.6 Alarm information

The Web Alarm menu provides the alarms that are active on site. For a full alarm description with actions see section Alarm list. The Web Alarm menu provides information about Active alarms and the time when an alarm is activated.

4.7 Graphs

The Web Graph provides the graphs shown in the table below. Enter the number of days to display in the graphs and click Submit. The default graphs present data for a period of one day.

Information shownComment
Graph – TemperaturesShows Connection Compartment, battery and outside temperature for the chosen amount of days.
Graph – PowerShows consumed power, genset 1–2, grid and solar power for the chosen amount of days.
Graph – GridShows grid voltage and current for the chosen amount of days.
Graph – Genset 1–2Shows genset voltage and current for the chosen amount of days.
Graph – BatteryShows system voltage, battery voltage, state of charge and charge current for the chosen amount of days.
Graph – Tank VolumeShows tank volume for the chosen amount of days.

The graphs provides data for a certain period in order to perform troubleshooting and to interpret the alarms. The example in figure 4.3 shows the recorded temperature data for a period of ten days.

Figure 4.3. Temperature data from the battery and ambient temperature sensors, recorded over a 10-day period.

4.8 About

The About menu provides the information shown in the table below.

Information shownComment
Software Versions– Main controller SW Version - Linux Version
Main Controller Information– System Cpu Load - System Cpu RAM Usage - System Cpu Temperature - System Sys Disk Usage - System Data Disk Usage - System Uptime - MAC address
HW Info– Main compartment serial number - Modem signal strength
License InformationInformation about open source software components that are used.

If the modem signal is acceptable, the modem signal strength is displayed in dB. If there is an error it is shown under this menu.

4.9 Configurations

Under the Configuration tab, the settings required for eSite x10 and its associated systems are made.

4.9.1 Overview

Current settings and values are visible in the 'Current value' column. To update settings and values, enter the new information in the column Set and click Save to confirm the update. The Save button must be clicked for each configuration.

4.9.2 Configuration content

Site Info

eSite Tools

Inputs/Outputs

Genset

Grid

Solar - Green Power Influx

Solar - External Solar

Cabinet Cooling

Fuel monitoring

Tenant

Battery

Load disconnect

Modbus communication

Shutdown/Restart

System update

Site commissioning

ℹ️ Note

Some configurations are optional and will not be shown if the option is not active.

4.9.3 Site Info

Use this configuration menu to change the name, location and time of eSite x10.

ConfigurationDefaultOption/rangeComment
eSite nameNot Commissioned-Name of the site.
Longitude0.0Longitude range -180 to 180Enter as decimal degrees. Use format (-)xx(x).xxx(xx).
Latitude0.0Latitude range 90 to 90Enter as decimal degrees. Use format (-)xx(x).xxx(xx).
Select time zoneAfrica /LibrevilleN/ASelect correct time zone from the drop down list.
Time/DateN/AYear - Month - Day Hour : min : secThe last known local time is automatically used.
Connection Compartment Serial Number0--
x10 ExpansionNo Expansion installedACDC Expansion installedEnable if x10 Expansion unit is installed

4.9.4 eSite Tools

Use this configuration menu when connecting eSite x10 to a specific eSite Tools server.

ConfigurationDefaultOption/rangeComment
eSite Tools IDNot CommissionedMust be unique for the site. Used to reference the site by eSite Tools server.
eSite Tools server IP0.0.0.0IP address to eSite Tools server. Provided by eSite Power Systems
eSite event time20 secThe time between events is synchronized between eSite x10 and eSite Tools.
IP number to NTP serverpool.ntp.orgRetrieves correct time using network Time Protocol (NTP).
Enable eSite Tools server timeOffOff / OnUse server time locally on site. The server time can differ from local site if the server is placed in another time zone.
Restart eSite Tools agentRestarts eSite Tools agent. After a restart it directly tries to establish a connection to the server.
Start eSite Tools communication test--This will start the communications test to eSite Tools. A log file is created and will be included in the backup archive, goto 'System' menu to backup data. The test can take up to 75 seconds.

4.9.5 I/O

Use this configuration menu when updating the I/O settings. For more information about I/O see 8.12.4 I/O screw terminals where the connection is made.

4.9.5.1 Inputs

ConfigurationDefaultOption/rangeComment
Source AAC gridNo Source / AC grid / AC genset 1Type of AC source connected to input A.
Source BNo sourceNo Source / AC grid / AC genset 2Type of AC source connected to input B.
Number of external Battery Current SensorNo External SensorNo External Sensor / One Sensor installed / Two sensor installedAt least one current sensor for each battery string is need to be mounted if an expansion unit is installed.
Battery 1 CAN sensorID 3C1ID 3C1-3C9Important to connect correct ID to the battery CAN sensor.
Battery 2 CAN sensorID 3C1ID 3C1-3C9Important to connect correct ID to the battery CAN sensor.
Battery Bank 1 MCBNormally closedNo input / Normally closed / Normally openWhen tripped the system is set to safe mode and an alarm is triggered.
Battery Bank 1 MCBNormally closedNo input / Normally closed / Normally openWhen tripped the system is set to safe mode and an alarm is triggered.
Battery Bank Door AlarmNormally closedNo input / Normally closed / Normally openWhen tripped an alarm is triggered.
Surge Protection AlarmNo inputNo input / Normally closed / Normally openUsed with external surge protection alarm. Check the I/O list for the connection. When tripped an alarm is triggered.
Aux Rectifier AlarmNormally closedNo input / Normally closed / Normally openUsed with external rectifier alarm. Check the I/O list for the connection. When tripped an alarm is triggered.
Battery Voltage SensorBattery Voltage SensorInternal Voltage Sensor/Battery Voltage SensorSelect which sensor to be used as battery voltage sensor. Internal uses x10 voltage sensor inside unit. Battery Voltage Sensor uses external battery voltage cables as sensor
Genset 1–2 Alarm 1–3No inputNo input / Normally closed / Normally openWhen tripped an alarm is triggered. Used for alarms coming from the genset using alarm relays. Same configuration can be found under section 'Genset'
Digital Inputs 1–8No inputNo input / Normally closed / Normally openConfigures the digital input to its corresponding relay wiring. If set to "No Input" alarms are not triggered.

4.9.5.2 Outputs

ConfigurationDefaultOption/rangeComment
Digital Output 1Genset 1 start cmdNot configurableUsed for genset start
Digital Output 2Not usedGenset 1 start cmd / Genset 2 start cmd / Green CC LED / Red CC LED / Cabinet Cooling / Alarm relay*See comments below.
Digital Output 3Green CC LEDGenset 1 start cmd / Genset 2 start cmd / Green CC LED / Red CC LED / Cabinet Cooling / Alarm relay*See comments below.
Digital Output 4Red CC LEDGenset 1 start cmd / Genset 2 start cmd / Green CC LED / Red CC LED / Cabinet Cooling / Alarm relay*See comments below.
Digital Output 5Not usedGenset 1 start cmd / Genset 2 start cmd / Green CC LED / Red CC LED / Cabinet Cooling / Alarm relay*See comments below.
Digital Output 6Not usedGenset 1 start cmd / Genset 2 start cmd / Green CC LED / Red CC LED / Cabinet Cooling / Alarm relay*See comments below.
Digital Output 2-6 StateNormally openNormally closed / Normally openFunction of the digital out relay.
Alarm Relay 2-6NoneSee section 6 Alarm listChoosing one alarm from the list will trigger an alarm on digital out relay.

*The digital out relays can be used to trigger an external alarm. The relay should not be connected directly to the alarm due to the current limitation through the relay. See 8.12.4 I/O screw terminals for more details.

4.9.6 Genset

Use this configuration menu to change the genset configuration. All gensets connected to eSite x10 are visible here, named Genset 1 and Genset 2. Click the genset to configure. This option is also used to update the Night Silence configuration.

ConfigurationDefaultOption/rangeComment
Night silence enableOffOff / OnEnables Night Silence mode.
Start time20:0000:00 – 23:59Start time for silent period. The batteries are pre-charged before this time.
Stop time08:0000:00 – 23:59Stop time for silent period. The genset is allowed to start.
Stop voltage level46.8 V0 – 60 VIf the battery voltage falls below this value the genset is allowed to start and the silence period ends. Only applicable if stop on charge request is disabled.
Stop SOC level00 – 100 %If the SOC level falls below this value the genset is allowed to start and the silence period ends. Only applicable if stop on charge request is disabled.
Min Capacity Left150 Ah0 – 9999 AhNight silence mode will end when a charge request becomes active
Stop on charge requestOnOff / OnSelect if a charge request is allowed to start the genset and end the night silence period.
Enable Exercise RunOffOff / OnEnable the genset exercise run
Interval between starts360 hours0 – 9999 hMinimum interval between genset starts.
Genset run duration1800 sec0 – 9999 sGenset running time.
Genset start alarm delay time300 sec1-9999 sGenset Failed to Start/Stop Alarms are trigged when the conditions are fulfilled after this time. Setting this time to a low value in a dual genset system will result in a quicker genset start. Recommended in UPS mode.
Operational modeAutoAuto / Genset Forced on / All AC sources OffUsed to force genset on from eSite. It is recommended to always leave operational mode in Auto.
Genset rated power15 kVA0 – 30kVARated power of genset. The power should not be set higher than the genset capacity. When calculate the genset rated output, only 70% of the total capacity is used.
Genset warm up10 sec0 – 600 secTime from genset start until power is drawn from it.
Genset ramp up30 sec0 – 600 secTime for gradually increasing power demand from genset.
Genset ramp down30 sec0 – 600 secTime for gradually decreasing power demand from genset.
Genset cooldown60 sec0 – 600 secTime the genset is running without any power demand before it is commanded off.
Genset service time250 h0 – 9999 hAlarm is trigged when this number of hours is left until service.
Genset Alarm 1–3No inputNo input / Normally closed / Normally openWhen tripped an alarm is triggered. Used for alarms coming from the genset using alarm relays. Same configuration can be found under section 'I/O'.
Genset service time resetN/AReset functionResets service time. The service time is presented on the genset page.
Genset run time resethoursSet/Reset functionSet the genset runtime to a value.
Genset service time alarm0 h0 – 1 000 hHours left until the service alert informs. Available only if the alarm is enabled.
Genset service time alarm enableDisabledEnabled / DisabledEnable the service time alarm.
Activate Genset control panel communicationDisabledEnabled / DisabledActivates genset control panel communication. See the Appendix for more information.
Slave ID11 – 255The slave ID must match the slave ID setting on the genset panel.
Restart Modbus communication after changesA restart after change of settings.

4.9.6.1 AMF panel communication

A set of signals can be configured to be read from the genset panel if they are supported from the genset panel. The following settings must be done for each signal according to the genset panel Modbus communication specification. See the Appendix For installation guide.

Signal nameAll available signalsSelect signal to configure
FunctionNo_Function / Read_Holding_Registers / Read_Input_RegistersSelect the correct function according to genset panel.
Register0 – 99 999The signal register.
TypeBOOLEAN / UINT8 / UINT16 / INT16 / UINT32 High word first / INT32 High word first / UINT32 Low word first / INT32 Low word first IEEE–754Select the signal type.
ScaleNo scale, 10, 100, 1000, 3600For signal scaling.
Bit position1 – 16Select the bit position.

4.9.7 Grid

ConfigurationDefaultOption/rangeComment
Maximum grid phase current19 A0 – 19 ACurrent limitation for the grid fuse of a single phase.

4.9.8 Solar

4.9.8.1 Green Power Influx

ConfigurationDefaultOption/rangeComment
Green Power Influx EnabledOffOn / OffEnables Green Power mode.
Green Power ModeLoad percentLoad Percent / Time Interval / AC Power MinimizationAllows the user to choose between the three available operational modes.
Voltage Activation49V0 – 60 VBattery voltage required for activation of green power influx function.
Voltage Deactivation47 V0 – 60 VIf the battery voltage goes below this value, Green Power mode is deactivated and the AC source must complete it's charge cycle before Green Power mode is reactivated.
SOC Level Activation60 %0 – 100 %If Green Power mode is inactive due to low SOC , it is activated when the SOC reaches this value.
SOC Level Deactivation50 %0 – 100 %Green Power mode is deactivated if the SOC level falls below this value.
Activation Delay Timer60 s0 – 3 600 sTime needed to ensure that solar power is stable and sufficient.
Solar Load Deactivation70 %0 – 200 %Solar power percentage of customer load required for solar to be considered sufficient. If Green Power mode is active, it is deactivated when the solar power drops below this limit. If Green Power mode is inactive, it is activated when this limit is exceeded and the specific mode requirements are met.
Solar Load Activation80 %0 – 200 %Solar power percentage of customer load required for Green Power mode deactivate.
AC Source Disable Time07:0000:00 – 23:59Green Power mode is activated, AC sources are disabled.
AC Source Enable Time16:3000:00 – 23:59Green Power mode is deactivated, AC sources are re-enabled.
Minimum SOC 40 %0 – 100 %Minimum SOC threshold for allowing AC Power in AC Minimization mode.
Minimum SOC Hyst.2 %0 – 100 %Minimum SOC hysteresis in SOC % for controlling AC Power inhibits in AC Minimization mode.

4.9.8.2 Solar - External Solar

ConfigurationDefaultOption/rangeComment
Enable external solar 1 and 2OffOn / OffSelect "On" only if an external solar is installed on site.
Solar 1 and 2 CAN sensorNo External SensorNo External Sensor / ID 3C1 - 3C9Set Solar 1 and 2 current sensor CAN ID. Make sure the ID is not in conflict with other CAN sensors.

4.9.9 Cabinet Cooling

Cabinet Cooling can be configured in two different modes, see table below. The digital output relay need to be configured to 'Cabinet Cooling', see I/O Configuration

ConfigurationDefaultOption/rangeComment
Cabinet Cooling modeNo Cabinet CoolingNo Cabinet Cooling, Delta Ambient, Battery temp levelsDelta Ambient mode uses temperatures offsets between battery and ambient temp. Battery Temp Level mode use an temperature set value.
Fan On Delta mode (°C)8°C0-100°CTemperature difference threshold for turning on battery cooling.
Fan Off Delta mode (°C)2°C0-100°CTemperature difference threshold for turning off battery cooling.
Fan On Level mode (°C)32°C0-100°CTemperature threshold for turning on battery cooling.
Fan Off Level mode (°C)25°C0-100°CTemperature threshold for turning off battery cooling.
Min Fan Runtime (sec)30010000 (sec)Minimum runtime for battery cooling fan before it can be turned off.
Manually start cooling fanCurrent output valueAuto, Cooling Fan OnThe output value can be: Off, On, Forced On, Fallback (temp sensor in fallback)

4.9.10 Fuel monitoring

Use this configuration menu to change the Fuel monitoring. All tanks connected to eSite x10 are visible here, named Tank 1 and Tank 2. Click the tank to configure. Two tanks can be installed with fuel monitoring with support for different types of sensors. A sensor with an output can be connected to an Analogue In on the I/O screw terminals. The measuring range of the Analogue In is 0 – 10 V. eSite x10 can also read fuel data from the genset panel if a fuel sensor is integrated with the genset. See section Genset Management.

ConfigurationDefaultOption/rangeComment
Sensor typeNo fuel sensorNo fuel sensor / Volt–height / Volt-litre / Lookup volt-litreAll counters for consumption, fillings and losses are reset when no fuel sensor is selected. Volt–height is used for standard sensor with an voltage output corresponding to pressure or height. Volt–litre is used with sensors that have an voltage output corresponding to litres. Lookup volt – litre is used for example on tanks of irregular shape.
Tank shapeRectangular boxNo tank / Rectangular box / Standing cylinder / Horizontal cylinderShape of the tank.
Tank height0 mm0 – 10 000 mmEnter the values as accurately as possible. Do not round off numbers.
Tank length0 mm0 – 10 000 mmEnter the values as accurately as possible. Do not round off numbers.
Tank width0 mm0 – 10 000 mmEnter the values as accurately as possible. Do not round off numbers.
Tank radius0 mm0 – 10 000 mmOnly available for cylindrical tank types. The radius can be calculated by measuring the circumference and divide by 2π.
Sensor max height1 884 mm0 – 10 000 mmFor pressure sensor the height is calculated as:
h = P/(ρg)
where P is pressure in Pasqual (Pa).
In the fuel sensor datasheet the range can be specified in Pa, Bar mH 2 O etc. Default for g is 9.812 and the density of diesel (rho) is 866 kg/m 3 . The density of diesel can vary.
Sensor output volt min0.1 V0 – 10 VIf a sensor with voltage as output is selected these settings must be set.
Sensor output volt max10 V0 – 10 VIf a sensor with voltage as output is selected these settings must be set.

4.9.11 Tenant

ConfigurationDefaultOption/rangeComment
Enable tenant 1 – 6 current sensorOffOn / OffIf a tenant sensor is installed, set to "On".
Configure CAN IDID 0-9ID 3C0 - 3C9Each tenant sensor has to be configured with the correct sensor ID. Use the dropdown list to select the correct CAN ID.
Total load high power alarm10 000 W0 – 21 000 WCombined power for both LP and HP and for all tenants. Must be active for 10 seconds. Threshold for high load alarm.
Tenant 1 – 6 high power alarm5 000 W0 – 9 500 WOnly active if tenant current sensor is "On". Must be active for 10 seconds. Threshold to trigger high power alarm.

4.9.12 Battery

Use this configuration menu to change the Battery settings. For custom battery configuration see below.

ConfigurationDefaultOption/rangeComment
Battery configurationNONEA battery template must always be selected. Select it from the dropdown list and press the button. Imported battery configurations will be visible at the end of the list.
Import battery configurationPress the link to import a new battery configuration file. The file must have the extension '.flx' and been created via the Export link or supplied from eSite Power Systems. The new configuration will be visible at the end in the dropdown list. For more information on how to save a custom battery configuration file see section System Update.
Export battery configurationPress link to create new battery configuration file from current battery values. For more information on how to save a custom battery configuration file see section System Update.
Battery charge strategyVoltage cycleVoltage cycle
Static SOC
Partial SOC
UPS AC mode
Different strategy will be visible depends on selected battery configuration. Reed section 8.4 Batteries for more information.
Start a full charge cycleManually trigger a full charge cycle. Recommended for new batteries. When started, system mode reports Auto Full Charge and charge mode on battery page reports Full Charge.
Start an extended full charge cycleManually trigger an extended full charge cycle. When started, system mode reports Auto Full Charge and charge mode on battery page reports Extended Full Charge.
Start Balancing Full Charge cycleManually trigger a Balancing Full Charge cycle for Li-ion batteries. When started, system mode reports Auto Full Charge and charge mode on the battery page reports Balancing Full Charge.
Reset number of charge cyclesReset number of completed charge cycles (Li-ion batteries only).
Enable Periodic Balancing Full ChargeEnable periodic Balancing Full Charge cycles (Li-ion batteries only).
Balancing Full Charge Energy ThroughputEnergy throughput between Balancing Full Charge cycles (Li-ion batteries only).
Balancing Full Charge Number of Cycles IntervalNumber of charge cycles between Balancing Full Charge cycles (Li-ion batteries only).
Alarm Battery High Temp°CSee data sheet of batteryAbove this level an alarm is triggered
Alarm Battery Very High Temp°CSee data sheet of batteryAbove this level an alarm is triggered
Alarm Battery Low VoltageV0-60VLow voltage alarm
Alarm Battery Low Voltage ResetV0-60VLow voltage alarm reset
Reset Battery Total ThroughputReset Battery Total Throughput

4.9.12.1 Lead-Acid battery parameters.

ConfigurationUnitRecommended valueDescription
Set new battery configuration name-any text > 3 lettersSet any name to the configuration setup, especially when the configuration shall be exported to other sites but not a requirement.
Rated CapacityAhSee data sheet of batteryRated of the battery string/BMU
Coulomb EfficiencySee data sheet of batteryCoefficient for compensating Ah round trip efficiency during charging. % * 0.01
Absorb VoltageVGenset/Grid boost voltage – 0.5VAbsorb voltage threshold
Absorb Timesec300 sAbsorb time(s)
Absorb To Charge VoltageVGenset/Grid float voltage – 0.5VFall back voltage
Equalize CurrentARated Battery Capacity * 0.03Equalize current
Equalize Timesec21600 (6h)Equalize time(s)
Fully Charged CurrentARated Battery Capacity * 0.03Full charge current
Fully Charged Timesec60Fully charged time(s)
Temperature Compensation X0-X3°CX1>X0, X2>X1, X3>X2Temperature compensation, X values, must be increasing with the lowest value in X0.
Temperature Compensation Y0-Y3VSee data sheet of batteryVoltage compensation, Y values
Extended Full Charge Timesec64800 (18h)Extended full charge time(s)
Genset Boost VoltageVSee data sheet of battery. Max 58VBoost voltage (topping charge with constant voltage level)
Genset Float VoltageVSee data sheet of batteryFloat voltage
Grid Boost VoltageVSee data sheet of battery. Max 58VBoost voltage (topping charge with constant voltage level)
Grid Float VoltageVSee data sheet of batteryFloat voltage
Solar Boost VoltageVGenset/Grid boost voltage + 0.2VSolar boost voltage
Solar Float VoltageVGenset/Grid float voltage + 0.2VSolar float voltage
Nominal CurrentARated Battery Capacity * 0.2Nominal battery charge current. VRLA: Total battery block current.
Maximum charge currentARated Battery Capacity * 0.2Battery charge current. Lithium-Ion: Set current upon total block size. Use current limit information from Li-ion batteries if present on com bus.
Safe Mode CurrentASame as Nominal CurrentUsed when the system is in an abnormal state
Safe Mode VoltageV< Float Genset VoltageUsed when the system is in an abnormal state
Voltage ControlUnitRecommended valueDescription
Start VoltageVSee data sheet of batteryVoltage level for charge start.
Stop VoltageVSee data sheet of battery OR Boost Voltage - 1VVoltage level for charge done. Stop when Voltage and Current are fulfilled.
Stop CurrentASee data sheet of battery OR Rated Battery Capacity/100Current level for charge done. Stop when Voltage and Current are fulfilled.
Stop TimesecSee data sheet of batteryCharge time(s) after reaching stop voltage/current
Full Charge Timesec864000 (10 days)Time(s) between full charge cycles
Full Charge EnergykWhRated Battery Capacity * 1.18Energy throughput between full charge cycles
Static SOCUnitRecommended valueDescription
Start SOCpercentSee data sheet of batterySOC level to start charge
Stop SOCpercentSee data sheet of batterySOC level to stop charge
Full Charge VoltageVSee data sheet of batteryLower voltage level to force full charge
Full Charge Timesec864000 (10 days)Time(s) between full charge cycles
Full Charge EnergykWhBattery Capacity * 1.18Energy throughput between full charge cycles
Partial SOCUnitRecommended valueDescription
SOCWindowpercentSee data sheet of batteryFalling SOC window to start charging
Stop CurrentASee data sheet of battery OR Rated Battery Capacity/100Current level for charge done. Stop when Voltage and Current are fulfilled.
Stop VoltageVSee data sheet of battery OR Boost Voltage - 1VVoltage level for charge done. Stop when Voltage and Current are fulfilled.
Inhibit Stop Chargingpercent35 %Lower SOC level to keep charge request
Full Charge VoltageVSee data sheet of batteryLower voltage level to force full charge
Full Charge Timesec864000 (10 days)Time(s) between full charge cycles
Full Charge EnergykWhRated Battery Capacity * 1.18Energy throughput between full charge cycles
UPS AC modeUnitRecommended valueDescription
Dual Genset Run Intervalsec21600 s (6 h)The time in seconds the genset shall run before switching genset. Max 99999999 s
Periodic Full Charge EnabledDisabledEnable the periodic full charge option
Full Charge Durationhours12 hThe time in hours the system shall run the genset in full charge mode.
Interval between Full Chargehours2160 h (90 days)Time between full charge cycles.
Full Charge Trigger VoltageV45.5 VMinimum=45 V, Maximum=60 V.

4.9.12.2 Lithium-ion battery parameters.

ConfigurationUnitRecommended valueDescription
Set new battery configuration name-any text > 3 lettersSet any name to the configuration setup, especially when the configuration shall be exported to other sites but not a requirement.
Rated CapacityAhSee data sheet of batteryRated of the battery string/BMU
Coloumb EfficiencySee data sheet of batteryCoefficient for compensating Ah round trip efficiency during charging. % * 0.01
Genset Set VoltageVSee data sheet of battery.Used in Lithium-Ion settings when using genset power
Genset Float VoltageVSee data sheet of battery.Used in Lithium-Ion settings when using genset power
Solar Set VoltageVSee data sheet of battery.Used in Lithium-Ion settings when using solar power
Solar Float VoltageVSee data sheet of battery.Used in Lithium-Ion settings when using solar power
Grid Set VoltageVSee data sheet of battery.Used in Lithium-Ion settings when using grid power
Grid Float VoltageVSee data sheet of battery.Used in Lithium-Ion settings when using grid power
Enable Battery Synchronization-DisabledEnable battery synchronization at the end of a charge cycle.
Battery Synchronization CurrentA0 ABattery synchronization charge current limit.
Battery Synchronization Timesec300 sBattery synchronization step duration.
Battery Ramp Up VoltageVolt50 VBattery ramp up start voltage.
Battery Ramp Up Timesec1sDefines the rate of voltage increase during ramp up. 1 Volt per configured time interval
Safe Mode CurrentASame as Nominal CurrentUsed when the system is in an abnormal state
Safe Mode VoltageV< Float Genset VoltageUsed when the system is in an abnormal state
Enable Hybrid Shifting-Disabled/EnabledHybrid shifting set a temporary genset stop value. See details in Battery reference section.
Set Shifting On timehh:mm-Time setting to activate hybrid shifting.
Set Shifting Off timehh:mm-Time setting to deactivate hybrid shifting.
Genset stop voltageV-Genset stop Voltage in Hybrid shifting mode.
Enable Peak Load Shifting-Disabled/EnabledPeak Load shifting set a temporary grid float value. See details in Battery reference section.
Set Shifting On timehh:mm-Time setting to activate peak load shifting.
Set Shifting Off timehh:mm-Time setting to deactivate peak load shifting.
Grid Float voltageV-Grid Float Voltage in Peak Load shifting mode.
BMS settingsUnitRecommended valueDescription
Charge State CurrentA1ABattery charge current threshold to be exceeded for the battery to be in Charge state.
Discharge State CurrentA-1ABattery discharge current threshold to fall below for the battery to be in Discharge state.
Charge Timesec10sDuration of charge or discharge current conditions to be valid until battery state changes.
Fully charged cut offARated Battery Capacity * 0.04Threshold of battery charge current to fall below for the battery to be considered fully charged..
Fully charged voltageVSee data sheet of batteryThreshold of battery voltage to be exceeded for the battery to be considered fully charged.
Fully charged time delaysec60 sDuration of the battery fully charged current AND fully charged voltage conditions to be met for the battery to be considered fully charged.
Equilibrium VoltageV0.1 VLimit of voltage increase/decrease rate for the battery to be considered to be in Equilibrium state.
Equilibrium Timesec300 sDuration of low voltage increase/decrease rate for the battery to enter Equilibrium state.
Voltage ControlUnitRecommended valueDescription
Start VoltageVSee data sheet of batteryVoltage level for charge start
Stop VoltageVSee data sheet of batteryVoltage level for charge done. Stop when Voltage and Current are fulfilled.
Stop CurrentASee data sheet of batteryCurrent level for charge done. Stop when Voltage and Current are fulfilled.
Stop TimesecSee data sheet of batteryCharge time(s) after reaching stop voltage/current
Static SOCUnitRecommended valueDescription
Start SOCpercentSee data sheet of batterySOC level to start charge
Stop SOCpercentSee data sheet of batterySOC level to stop charge
Static SOCcontrol options-21 = Start/stop on average SOC, 2 = Protective SSOC with active comm. Start/stop on min/max BMU SOC, 3 = Balancing SSOC with active comm. Start/stop on min/min BMU SOC.
Balancing Full Charge Trigger VoltageV45.5 VSafety SOC level to trigger Balancing Full Charge

4.9.13 Load disconnect

Low voltage disconnect settingsUnitRecommended valueDescription
Low Prio load disconnect voltV42-60 VVoltage to disconnect LP, default=45 V
Low Prio load disconnect timesecTime before LP is disconnected after disconnect thresholds are reached, default=300 s
Low Prio load reconnect voltV42-60 VVoltage required to reconnect LP, default=48 V
Low Prio load reconnect timesecTime before LP is reconnected after reconnect thresholds are reached, default=30 s
Low Prio load reconnect currentA0-200 AProduced current required to reconnect LP, default=20 A
Low Prio load fast reconnect voltV42-60 VVoltage required for fast reconnect of LP , default=52 V.
High Prio load LVD enable-DisabledIf enabled, LVD will use separate settings for High Prio load LVD. Disabled, LVD will use the same settings for High Prio load as for Low Prio load.
High Prio load disconnect voltV42-60 VVoltage to disconnect HP, default=43.5 V
High Prio load disconnect time secsecTime before HP is disconnected after disconnect thresholds are reached, default=5 s
High Prio load reconnect voltageV42-60 VVoltage required to reconnect HP, default=48 V.
High Prio load reconnect time secsecTime before LP is reconnected after reconnect thresholds are reached, default=5 s

4.9.14 Modbus Communication

The Modbus communication enables third party systems to communicate with eSite. Use this configuration menu to change the Modbus settings. For more information regards the server registry see separate manual "eSite x10 Modbus server".

4.9.14.1 Modbus/RTU RS-485 settings

ConfigurationDefaultOption/rangeComment
Enable communication to Li-ion BMSOFFON / OFFSet to ON if communication to Li-ion BMS is installed.
Installed Li-Ion modules01-255Number of installed BMUs, used to set communication alarms and for communication to BMU.
Enable communication to Genset1 AMF panelOFFON / OFFSet to ON if communication to Genset1 is installed. Configuration needed in Genset tab.
Enable communication to Genset2 AMF panelOFFON / OFFSet to ON if communication to Genset2 is installed. Configuration needed in Genset tab.
Slave ID01-255The slave ID must not be in conflict with any ID on the Modbus.
Restart Modbus handlerRestart Modbus handler when changes are made.

4.9.14.2 Modbus Server

ConfigurationDefaultOption/rangeComment
Set Modbus / RTU or Modbus / TCPRTURTU / TCPSet Modbus server protocol.
Server port number15021 – 9 999Set Modbus server port number.
Server slave ID11 – 999Set Modbus server slave ID.
Enable Modbus serverOffOn / OffEnable / disable Modbus server.
Restart Modbus serverRestarts Modbus server when changes are made..

ℹ️ Note

Modbus Server/Slave uses to serve data to an external client, a data sheet can be requested from eSite Power Systems. The server can not be running in Modbus/RTU at the same time as an AMF Genset panel or Li-ion communication via Modbus/RTU is active. Make sure the Modbus server is OFF at that time or communicate via TCP. It is not possible to select RTU when Modbus is already active by Genset or Li-ion Modbus/RTU communication.

4.9.15 Shutdown/Restart

Use this configuration menu when eSite x10 must be shutdown or restarted.

ConfigurationComment
Reboot systemReboot main controller.
Shutdown systemShutdown main controller. To boot up after a shutdown, power to the Main Compartment must first be turned off.
Factory resetReset all configurations to default settings. eSite x10 will reboot afterwards.
Modem restartRestart the modem.
Reset Load switchIf one or both of the LP and HP load breakers are tripped due to over-current, pressing the reset button will reset the breakers and reconnect the load.

4.9.16 System update

Use this configuration option to perform a system update, backup data and upload configuration data.

See section System Update for more information.

ConfigurationComment
Update eSite x10 controllersUpdate the main controller, rectifier and solar controllers. Update images are provided by eSite Power Systems.
Backup dataBackup configuration data, custom battery file, Modbus configuration file and log data.
Upload configuration dataUpload a new battery file or configuration files received from eSite Power Systems here.
Update eSite x10 licenseUpdate the License file. The file, which is provided by eSite Power Systems, must match the serial number of the eSite x10.
Change passwordSelect a user to change its password. Write the new user password in the text box and press 'Save'
Reset passwordsReset passwords. Select a user and press 'Reset' button.
Add IP address/subnet maskAdd an extra ip address to eth0. Use syntax: xxx.xxx.xxx.xxx/nn where x is the IP address and nn is the subnet mask in Linux notation (24 = mask 255.255.255.0).
Add IP gatewayAdd a gateway to eth0. Use syntax: xxx.xxx.xxx.xxx where x is the IP address to the gateway
IP RestorePress to restore default IP settings
Change APN settingChange the modem access point name (apn) from default (internet). Be patient, it takes 30 seconds to restart the modem with new settings.

4.9.17 Site Commissioning

This page forwards you to the site commissioning guide. During site commissioning eSite x10 configurations are finalized. The site commissioning makes sure that the eSite x10 is set up correctly and operates as intended.



Copyright © 2021 eSite Power Systems AB